Abstract

This paper describes a new algorithm to calculate the per phase impedance between the measurement and fault points on a transmission line, featuring robustness to the uncertainties in load current and fault path resistance. The algorithm, which is ideal for distance relaying, is derived based on a justifiable assumption of the fault path being purely resistive, implying that the unmeasured fault point voltage and fault path current are in phase with each other. This paper illustrates the characteristics of the proposed algorithm and evaluates its performance by using PSCAD/EMTDC simulation.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.