A new line of SF6 breakers has been developed to cover the range of 34.5 to 69 kv and 500 to 2,500 mva (megavolt-amperes). A new puffer-type interrupter is used to operate in sealed and grounded metal tanks at 60 psig (pounds per square inch gage) gas pressure. Interrupting tests and impulse voltage withstand tests have been made according to proposed new ASA (American Standards Association) standards. Capacitor switching tests have been made which show these breakers to be well suited for switching large single or multiple banks.

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.