Abstract

In this paper, new current limiting strategy is proposed to improve fault ride-through capability and moreover, a generalized fault model is presented for droop-controlled and directly voltage controlled inverter-interfaced distributed energy resources to be used in the protection studies. The previously reported fault models almost did not consider the effect of control system in depth. An improved hierarchical droop-based control scheme is presented which includes a complementary stabilizing control loop. Also, a brief review for reported directly voltage-controlled schemes is provided. Moreover, a current limiting strategy is proposed that can be implemented in different reference frames. As a special case, fault contributions of wind and solar units are investigated and special recommendations are provided. Finally, the presented fault model is analytically tested for three-wire and four wire inverter topologies and various types of faults and then verified by offline time-domain simulations in MATLAB/SIMULINK environment and thereafter, validated by the investigation through real-time digital simulations using OPAL-RT simulator.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.