Abstract

A current-mode control power convertor model that is accurate at frequencies from DC to half the switching frequency is described for constant-frequency operation. Using a simple pole-zero transfer function, the model is able to predict subharmonic oscillation without the need for discrete-time z-transform models. The accuracy of sampled-data modeling is incorporated into the model by a second-order representation of the sampled-data transfer function which is valid up to half the switching frequency. Predictions of current loop gain; control-to-output; output impedance; and audio susceptibility transfer functions were confirmed with measurements on a buck converter. The audio susceptibility of the buck converter can be nulled with the appropriate value of external ramp. The modeling concentrates on constant-frequency pulse-width modulation (PWM) converters, but the methods can be applied to variable-frequency control and discontinuous conduction mode.< <ETX xmlns:mml="http://www.w3.org/1998/Math/MathML" xmlns:xlink="http://www.w3.org/1999/xlink">&gt;</ETX>

Full Text
Published version (Free)

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call