Abstract

A new algorithm for protection against voltage collapse is proposed. The algorithm makes use of the magnitudes and angles of the local phasors, i.e. bus voltages and load currents. The change in an apparent-power line flow during a time interval is exploited for computing the voltage collapse criterion. The criterion equals zero when a voltage collapse occurs. The proposed algorithm could be easily implemented in a numerical relay. The information obtained by the relay can be used at two levels - for the coordinated system-wide control action or for automatic action on the local level. The algorithm is simple and computationally very fast. It was tested on the IEEE 118-bus test system.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.