Abstract

The paper begins with a review of techniques for computer based protection of multi-winding three-phase power transformers. After reviewing the principles of harmonic-restraint and voltage-restraint current differential protection, the paper develops a technique which computes and uses flux-current relationship of the transformer to obtain. the restraint function. It is shown that this protection technique requires fewer computations as compared to the harmonic current computation, and hence can be implemented on a microcomputer of modest. capability. The principle has been tested. in the'laboratory on a model power transformer. The relay based on this flux-restraint principle performs well on all the system phenomena simulated in the laboratory. It is expected that a relay based on this principle will be tested in the field on a power transformer.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.