Abstract
We proposed a new kind of coil type axial magnetic field (AMF) contact for 126 kV single break vacuum interrupters (VIs). The objective of this paper is to analyze and optimize AMF characteristics of the new contact. Compared with a former coil type AMF contact with 2 segments we developed, the new AMF contact is advantage with stronger AMF and lower electrode resistance. Its AMF characteristics were analyzed by finite element method (FEM) and we optimized AMF characteristics of the new contact by quadratic orthogonal regressive analysis. The optimization design results show that 1) the maximum axial magnetic flux density is 8.84 m T/kA on intermediate plane of contact gap 30 mm at current peak; 2) the maximum axial magnetic flux density is 1.18 m T/kA on intermediate plane of contact gap 30 mm at current zero; 3) the minimum electrode resistance is 7.8 muOmega.
Talk to us
Join us for a 30 min session where you can share your feedback and ask us any queries you have
Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.