Abstract

The problem of harmonic reduction is alternatively approached as an energy user’s problem. The user’s objective is to eliminate his voltage harmonic distortion problem locally without considering the effects of voltage distortion at neighboring buses. The remedy is insertion of a reactor in series with the local compensating capacitor. A method is presented for finding the optimum fixed LC combination to minimize voltage harmonic distortion at a load bus while holding the power factor at a desired value and constraining the compensator values which would create resonant conditions and the manufacturer’s standard values for power shunt capacitors.