Abstract

Abstract One of transient phenomena that lead to the false trip of the power transformer differential protection during the energization of a loaded power transformer is the ultra-saturation phenomenon. This paper presents, at first, a new algorithm for three-phase power transformer differential protection considering effect of the ultra-saturation phenomenon based on Discrete Wavelet Transform (DWT). To model the ultra-saturation phenomenon, the nonlinear characteristic of the transformer core and the effect of the saturation of the current transformers are taken into account. It is assumed that the load of the transformer is a resistive and inductive load. In this algorithm, the ultra-saturation phenomenon, the external and internal faults of power transformer and the magnetic inrush current are simulated. To distinguish between these phenomena, appropriate criteria using DWT by the use of standard deviation of coefficients are presented. Also, one of the most important criteria for the digital relays is the time for making a decision. Thus, to determine the time of decision, the experimental results will be presented.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.