Recent developments in anti-islanding techniques have demonstrated that phase shift techniques are very effective for anti-islanding protections in inverter-based distributed generation (DG) systems. Several approaches have been proposed in the previous researches such as slide-mode frequency shift (SMS), active frequency drift (AFD), and active frequency drift with positive feedback (AFDPF) etc. The automatic phase shift (APS) method is actually a modified SMS method. It can effectively reduce the non-detection zone (NDZ) of the SMS technique by introducing an additional phase shift increment each time the frequency of the terminal voltage stabilizes. However, it is very difficult to determine a stable islanding frequency, and the APS algorithm sometimes acts slowly, even fails in certain load conditions. A new adaptive logic phase-shift (ALPS) algorithm is proposed in this paper to regulate the additional phase shift at a suspicious islanding situation and evaluate the effects of the phase shift. This algorithm can yield a quick phase shift in an islanding situation yet only produce a very small phase shift when the grid is available for inverter-based DG systems. Both simulation and experiment results have proved the robustness and effectiveness of the newly proposed anti-islanding algorithm

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.