Abstract

A new nondestructive diagnosis method is developed mainly for stator coil insulation of high voltage rotating machines as a result of analysis and experience on the behavior of a current of a sample under ac voltage application. A newly-defined parameter Y, measured in this method, equals tan, plus y, where y closely relates to void volume ratio in a sample. A new apparatus to measure Y automatically is also developed which shows experimentally several advantages in a practical test. Y-V patterns and y-V patterns by this method are verified to correlate well to insulation condition and residual breakdown voltage of a sample.

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.