Abstract

The influence of nonuniform aging has not been considered in the prediction of the frequency domain spectroscopy (FDS) of the transformer oil-paper insulation (OPI) when using the finite element method (FEM). Given this issue, the modified simulation model was constructed based on the XY model and FEM. In the current work, the dielectric response property of the pressboards with different aging conditions in the modified model was characterized by its dielectric response parameters measured in the lab. Then the modified simulation model constructed in a 3-D system would be applied to study the effect of both nonuniform aging and the axial geometry on the FDS of OPI. Finally, the feasibility of the proposed models was verified by comparing the measured FDS and the predicted FDS. This article is expected to provide a model for predicting the FDS of the transformer OPI including the effect of nonuniform aging.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.