Abstract

Selective ground relays (SGRs) are useful fur distinguishing a faulted feeder from the sound feeders in ungrounded systems. However, they sometimes mis-operate due to human or device errors. Particularly, the reversed polarity of zero-sequence current transducers (ZCTs) is the most frequent cause of mis-operation. This paper presents a modified SGR for reducing the probability of mis-operations caused by the reversed polarity of ZCTs. The modification is achieved by introducing an adaptive time delay, which depends on the magnitude of the zero-sequence current and the phase angle deviation from the reference. The modified SGR was successfully demonstrated on a sample ungrounded system without mis-operation.