Abstract
The moment of vacuum breaker contacts opening to arc creating process is an unbalanced gaseous breakdown process. This before-arc process is the foundation of studying arc process. The mechanism of the metal vapor arc is different from other gas medium and contains complex electrode process. The proximal cathode region is the important area for vacuum arc forming and it is affected by many factors. The influences of the different electrode separations, different secondary emission coefficient on electronic density, electronic temperature and electric potential, were analysed in this paper. The simulation results show that the change of electrode separations barely impacts the thickness of sheath and the decrease of electrode separations will lead to the decrease of electronic energy near the cathode sheath. The increase of secondary electron emission will increase charged particles energy, which is the important condition of forming cathode sheath.
Talk to us
Join us for a 30 min session where you can share your feedback and ask us any queries you have
Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.