Abstract

An easy and swift method to evaluate, in a system of interconnected earth electrodes, earth potentials on earthing systems of medium-voltage/low-voltage (MV/LV) substations, in an event of single-line-to-earth fault inside a high-voltage/medium- voltage (HV/MV) station, is presented. The advantage of the method is the simplicity of the mathematical model for solving complex systems of any size with a sufficient accuracy for practical purposes. This paper shows the results of simulations, performed on networks with different extensions and characteristics, organized in easy-to-read graphs and tables. A comparison of these results with the values obtained according to the procedure explained in the IEC-Standard 60909-3, and a study on the accuracy of the method has been made. Moreover, some considerations on the inclusion of earth electrodes of HV/MV stations within global earthing systems are done.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.