Abstract

Due to excitation inrush current, no-load transformer accesses system can cause different degree of voltage sag. Therefore presents a method to estimate voltage sag caused by closing no-load transformer. Firstly, accord to the point of saturation magnetic flux and transformer core general single value curve equation to establish general nonlinear magnetization curve. Use the linear features of saturated magnetization curve segment to estimate the maximum inrush current and calculate the maximum depth of voltage sag. According to the magnetic flux decay time to estimate the duration of voltage sag. Simulate closing no-load transformer in a 10kV distribution network, and compare the simulated result with the calculated result. The results show that the proposed method is validity and accuracy.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.