Abstract

The method to identify the sources of the neutral-to- earth voltage (NEV) rise as presented in a companion paper is verified in this paper through extensive simulation studies and field measurements. Sensitivity studies are conducted to determine factors that affect the performance of the proposed method. The results show that the NEV contribution factor index is effective in identifying load unbalance caused NEV and its contributors. The current return ratio index is effective in diagnosing poor grounding caused NEV and its contributors. An NEV trouble shooting strategy and a system-wide NEV condition monitoring strategy are proposed based on the findings.

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.