Abstract

In this paper, it is shown that the maxnuma electric field under the six-phase line with a modified phase arrangement becomes as low as that under the three-phase double-circuit ( conventional ) line. Then, a method is proposed for limiting line-to-ground fault currents and short-circuit currents without causing the fall in unfaulted phase voltages in the six- phase system with its neutrals solidly grounded. The fault analysis and the experimental result demanstrate that for a single line-to-ground fault at the sending end, the fault current in the proposed system is half that in the conventional system. As for the three-phase short-circuit fault at the sending end, the fault current in the proposed system is about 60% of that in the conventional system. It is concluded that the proposed six-phase system is superior in the system transient stability to the conventional system.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.