Abstract

With the rapid development of the national economy, the system cabling rate continues to improve, the system capacitive current continues to increase, and the arc suppression coil grounding method is more and more widely used. Among them, the pre adjustable turn adjustable arc suppression coil accounts for the highest proportion. How to accurately, quickly and real-time measure and calculate the capacitive current of the system is the foundation to realize the automatic tracking and compensation of the arc suppression coil, It is also the key to reliably extinguish the arc and reduce the influence range of the fault when the single-phase grounding fault occurs in the system. Based on the analysis of the variation law of the capacitive current in the distribution network neutral grounding system through the arc suppression coil, this paper proposes a new method for measuring the capacitive current based on the resonance point curve fitting, which is suitable for the pre adjustable turn adjustable arc suppression coil grounding system, and verifies its reliability and accuracy through simulation.

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.