Abstract
In the resonant grounding system, the accurate judgment of arc-extinction time has guiding significance for the line selection of grounding fault, the evaluation of the arc suppression effect, and the extraction and utilization of transient information after arc extinction. Aiming at the single-phase grounding fault of resonant grounding system, this paper analyzes the frequence change characteristics before and after arc extinction. It is found that the frequence of zero-sequence electrical quantity before arc extinction is power frequence, and it changes after arc extinction. It is used to construct single-frequence methods and dual-frequence methods for judging arc-extinction time. As a tool for dynamic frequence measurement, SOGI-FLL is utilized to realize the engineering application of the method for judging arc-extinction time. The method’s accuracy is proved by Matlab/Simulink simulation and field test.
Talk to us
Join us for a 30 min session where you can share your feedback and ask us any queries you have
Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.