Abstract

A review is given of National Institute for Occupational Safety and Health (NIOSH) efforts to control N2O at a pediatric dental operatory from 1978 to the present. Measurements of N2O concentrations were made on four occasions before and after installation of different controls, using an infrared analyzer. Air velocity and volumetric flow measurements also were taken, Video imaging was done in some cases simultaneously with real-time N2O measurements to correlate work practices with exposure data. An infrared imaging system was used to identify sources of N2O. Critical components of resulting recommendations for control include monitoring of N2O concentrations; use of engineering controls, such as a scavenging mask, an effective dilution ventilation system, and auxiliary exhaust; good work practices; maintenance of the equipment; and worker education. Data presented strongly supports the hypothesis that better implementation of controls leads to reduction of N2O exposures. N2O concentrations were reduced by a factor of 61 from their initial levels. The current NIOSH recommended exposure limit of 25 ppm TWA during the time of N2O administration appears to be achievable.

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.