Abstract

A hybrid synchronously rotating reference frame (HSRRF)-based voltage sag detection is proposed in this paper. The proposed method provides the fast and accurate voltage sag detection even in the distorted grid voltage environments. A hybrid algorithm is used to improve the performance by a combination of the instantaneous voltage sag detection part and the synchronously rotating reference frame (SRRF)-based voltage sag detection part. If any instantaneous voltage sag is detected and the voltages from SRRF-based voltage sag detection part decreases to the reference value, then the completed voltage sag condition is recognized. This proposed voltage sag detection provides a shorter detection time in every condition when comparing to the conventional methods. The validation of proposed algorithm is confirmed through the computer simulations which are operated in the distorted grid voltages with various conditions of the voltage sag.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.