Abstract

With the increasing penetration of distributed generators in the smart grids, having knowledge of rapid real-time electromechanical dynamic states has become crucial to system stability control. Conventional Supervisory Control and Data Acquisition (SCADA)-based dynamic state estimation (DSE) techniques are limited by the slow sampling rates, while the emerging phasor measurement units (PMUs) technology enables rapid real-time measurements at network nodes. Using generator bus terminal voltages, we propose a hybrid-learning DSE (HL-DSE) algorithm to estimate the synchronous machine rotor angle and speed in real time. The HL-DSE takes the power system model into account and trains neuroestimators with real-time data in an online manner. Compared with traditional DSE methods, the HL-DSE overcomes limitations by using a data-driven approach in conjunction with the physical power system model. The time efficiency, accuracy, convergence, and robustness of the proposed algorithm are tested under noises and fault conditions in both small- and large-scale test systems. Simulation results show that the proposed HL-DSE is much more computationally efficient than widely used Kalman filter (KF)-based methods while maintaining comparable accuracy and robustness. In particular, HL-DSE is over 100 times faster than square-root unscented KF (SR-UKF) and 80 times faster than extended KF (EKF). The advantages and challenges of the HL-DSE are also discussed.