Abstract

This paper proposes hybrid islanding detection for inverter-based distributed generation (DG) units. Conventionally, passive islanding detection methods may fail when power mismatches are nearly zero. Also, the difficulty of setting threshold is another common problem. To overcome this drawback, a new procedure for islanding detection is proposed based on the combination of the rate of change of voltage (ROCOV) and the rate of change of active power (ROCOAP). The ROCOAP is only activated when the islanding condition is suspected by ROCOV. When the power mismatch is negligible, some high-impedance fault or non-islanding events occur, the proposed method can identify islanding, thus presenting a combination of advantages of each passive/active method. Therefore, it is useful to appropriately detect islanding situation in all-inclusive of scenarios. Consequently, the proposed method under several conditions, such as pulsating loads, pre-energized transformers have been considered. To illustrate the effectiveness of the proposed approach, various tests such as UL1741 have been investigated. Comparison analysis shows that the suggested method is more acceptable and the NDZ is reduced significantly. In addition, proper performance even for small power mismatch is illustrated by presence of variety of non-islanding events and improvement of power quality is achieved in comparison active method.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.