Abstract
In the multi-infeed LCC-HVDC system, the concurrent commutation failure (CCF) caused by the AC fault of the receiving-end system may lead to the blocking of multiple converter stations, which challenges power grid security and stability. This paper proposes a novel method to quickly and accurately identify the CF risk areas, considering the CF probability (CFP) during the single-line-to-ground (SLG) fault. First, an AC-DC voltage asymmetry factor (ADVAF) and its theoretical derivation are proposed to quantify the influence of the fault position on the CF. Second, the critical ADVAF (CADVAF) is derived based on the equivalent method. By comparing ADVAF and CADVAF, the CF risk areas can be quickly divided into non-, possible- and inevitable-concurrent CF risk areas. Third, the relationship between local CFP (LCFP) and fault position is established, and the concurrent CFP (CCFP) is calculated. The proposed method has improved the accuracy and computational efficiency of theoretical analysis than earlier methods. Finally, the validity and accuracy of the proposed method are verified in dual-infeed and five-infeed LCC-HVDC systems built based on the IEEE 39-bus and IEEE 118-bus models, respectively.
Talk to us
Join us for a 30 min session where you can share your feedback and ask us any queries you have
Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.