Abstract
<span lang="EN-US">Temporary voltage swells and sags appear with high frequency in electric power systems, and they significantly affect sensitive loads such as industrial manufacturing or communication devices. This paper presents a strategy to design proportional-resonant controllers for three full-bridge voltage-source converters with a common DC-link in dynamic voltage restorer systems. The proposed controllers allow the system to quickly overcome temporary unbalanced voltage sags. Simulation results carried out in MATLAB/Simulink and experimental results implemented in a Typhoon HIL402 device demonstrate the ability of the proposed design method. The results show that the system with the proposed controllers can ride-through single-phase or double-phase voltage sags up to 55% and three-phase voltage sags up to 70% in a duration less than one grid-voltage cycle.</span>
Talk to us
Join us for a 30 min session where you can share your feedback and ask us any queries you have
More From: International Journal of Power Electronics and Drive Systems (IJPEDS)
Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.