Abstract

AbstractAn enhanced fault location method based on voltage sag profiles for distribution networks is presented in this paper. In other previous methods, only a single measurement has been used. The proposed method can be used with any number of measurements in the network, making it more general. A new ranking approach that addresses multiple possibilities of the faulted section is proposed. Different case studies with various numbers of measurements are performed on a large 11‐kV network with the main feeder consisting of 42 buses to validate the method. The test results show that there is an improvement in terms of accuracy in detecting the faulted section in the first attempt for each additional measurement. Therefore, by utilizing the average value of each measurement, a better accuracy of fault location can be achieved. © 2013 Institute of Electrical Engineers of Japan. Published by John Wiley & Sons, Inc.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.