Abstract

Wide-area fault location (WAFL) refers to the estimation of fault distance on the faulted line using PMU data. A system of linear equations is formulated for WAFL, taking advantage of both voltage and current synchrophasors. This results in a generalized closed-form solution for the fault distance using the weighted least-squares method. The main contribution of the letter is the rigorous derivation of the equation weights based on the statistical distributions of the superimposed errors, i.e., the differences between the errors of the corresponding pre- and post-fault synchrophasors. The method's effectiveness, robustness against different factors, and superiority over existing methods are demonstrated by extensive simulations and comparison studies conducted on the IEEE 39-bus test system.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.