Abstract

Wet surface heat exchangers such as cooling towers and wet plate heat exchangers are important in air conditioning. A linear approximate model of wet surface heat exchangers is proposed. The equations of the model are rearranged, enabling solutions for wet bulb depression and wet bulb temperature to be obtained independently, by analogy from published solutions for dry bulb temperature in dry surface heat exchangers. Performance predictions by this method for a crossflow cooling tower are found to agree with those from a prevous finite difference solution. Published performance measurements for a crossflow wet plate heat exchanger are lower than predicted by the method possibly due to poor wetting or excessive water flow. Excellent performance is predicted for a proposed regenerative evaporative cooler using such an exchanger.

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.