Abstract

Time domain-based online dynamic security assessment (DSA) systems require a fast and reliable method for simulation termination and margin calculation. B.C. Hydro's online DSA uses the second kick method which proved to be an elegant and reliable method for this purpose. This method was later enhanced to improve implementation and computation requirements. The methods presented so far require the mode of disturbance (MOD) information. In this paper, the fast second kick method is expanded to remove the need for the MOD data. The new method has been tested on the large scale systems of B.C. Hydro and Hydro Quebec and the results have been compared to those of the fast second kick method. The results obtained indicate that the new method predicts the stability limits accurately. They also indicate that the new method takes in average 20% longer than the fast second kick method to calculate the stability limit. The implementation requirement for both methods is similar.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.