Abstract
Block specimen, hydrogen effusion, and model boiler experiments have shown that mild steel, after a brief period of “flash” oxidation immediately following immersion in aqueous solution, either corrodes relatively slowly with the formation of a thin, corrosion-resistant magnetite film, or corrosion proceeds rapidly with the development of a non-protective accumulation of iron oxide. In the latter case, film-destructive mechanisms induced experimentally by combinations of high temperature, stress, and quite high concentrations of hydroxide alkalinity or ferrous chloride have produced examples of generalized severe metal loss, pitting, heavy oxide accumulation, and hydrogen damage remarkably similar to corrosion manifestations responsible for metal failure in real boilers.
Talk to us
Join us for a 30 min session where you can share your feedback and ask us any queries you have
Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.