Abstract
Accurate modeling of hourly heating and cooling energy use in commercial buildings can be achieved by a Generalized Fourier Series (GFS) approach involving weather variables such as dry-bulb temperature, specific humidity and horizontal solar flux. However, there are situations when only temperature data is available. The objective of this paper is to (i) describe development of a variant of the GFS approach which allows modeling both heating and cooling hourly energy use in commercial buildings with outdoor temperature as the only weather variable and (ii) illustrate its application with monitored hourly data from several buildings in Texas. It is found that the new Temperature based Fourier Series (TFS) approach (i) provides better approximation to heating energy use than the existing GFS approach, ((ii) can indirectly account for humidity and solar effects in the cooling energy use, (iii) offers physical insight into the operating pattern of a building HVAC system and (iv) can be used for diagnostic purposes.
Talk to us
Join us for a 30 min session where you can share your feedback and ask us any queries you have
Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.