Abstract

The eco-mode provides a high-efficiency operation for the double-conversion uninterrupted power supplies (UPSs). Such a mechanism utilizes the solid-state transfer switch (STS) path to power the susceptible loads, and it relies on the converter as an alternate resource when the abnormal grid occurs. The thyristor-based STS system has the advantage of low conduction loss, but the natural commutation often prolongs the overall transfer process. Consequently, the susceptible loads suffer from severe grid faults for a long time. This article investigates the commutation mechanism between the thyristor-based STS system and the double-conversion UPS. A forced commutation control is presented to accelerate the transfer process through the back-to-back neutral-point clamped (BTBNPC) converter. Besides, the waveform qualities and the dynamics of both ac and dc ends are considered for the BTBNPC converter. Finally, the laboratory test results are provided to validate the effectiveness of the proposed approach.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.