The field performance of a low-flow internally cooled/heated liquid desiccant air conditioning (LDAC) system is investigated in this paper. The quasi-steady performance (sensible and latent heat transfer rates, coefficient of performance (COP), and uncertainties) of the LDAC system is quantified under different ambient air conditions. A major contribution of this work is a direct comparison of the transient and quasi-steady performance of the LDAC system. This paper is the first to quantify the importance of transients and shows that, for the environmental and operating conditions in this paper, transients can be neglected when estimating the energy consumption of the LDAC system. Another major contribution of this work is the development and verification of a new method that quantifies (with acceptable uncertainties) the quasi-steady performance of a LDAC system from transient field data using average data.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.