Abstract

This paper presents a new method for locating faults on three-terminal power lines. Estimation of a distance to fault and indication of a faulted section is performed using three-phase current from all three terminals and additionally three-phase voltage from the terminal at which a fault locator is installed. Such a set of synchronized measurements has been taken into consideration with the aim of developing a fault-location algorithm for applications with current differential relays of three-terminal lines. The delivered fault-location algorithm consists of three subroutines designated for locating faults within particular line sections and a procedure for indicating the faulted line section. Testing and evaluation of the algorithm has been performed with fault data obtained from versatile Alternate Transients Program-Electromagnetic Transients Program simulations. The sample results of the evaluation are reported and discussed.

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.