Abstract

This paper presents the results of a site survey study on the faults in variable air volume (VAV) terminals and an automatic fault detection and diagnosis (FDD) strategy for VAV air-conditioning systems using a hybrid approach. The site survey study was conducted in a commercial building. 20.9% VAV terminals were ineffective and 10 main faults were identified in the VAV air-conditioning systems. The FDD strategy adopts a hybrid approach utilizing expert rules, performance indexes and statistical process control models to address these faults. Supported by a pattern recognition method, expert rules and performance indexes based on system physical characteristics are adopted to detect 9 of the 10 faults. Two pattern recognition indexes are introduced for fault isolation to overcome the difficulty in differentiating damper sticking and hysteresis from improper controller tuning. A principal component analysis (PCA)-based method is developed to detect VAV terminal flow sensor biases and to reconstruct the faulty sensors. The FDD strategy is tested and validated on typical VAV air-conditioning systems involving multiple faults both in simulation and in situ tests.

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.