Abstract

Combined with an example of 750kV shunt reactor exception handling, the author used field test inspections and search methods to dismantle the plant and found that the cause of the reactor abnormality was an incident caused by impurities or foreign matter. Combining the historical operation data of the equipment, the analysis and comparison of the reactor’s routine inspections and test results are performed. Combined with the simulation calculation of the internal insulation margin of the reactor, the judgment methods and conclusions are given, and the troubleshooting method and flow of the reactor abnormality are proposed, and put forward specific measures to strengthen the state monitoring of the network operation reactor.