Abstract

Understanding the impact of distributed photovoltaic (PV) resources on various elements of the distribution feeder is imperative for their cost effective integration. A year-long quasi-static time series (QSTS) simulation at 1-second granularity is often necessary to fully study these impacts. However, the significant computational burden associated with running QSTS simulations is a major challenge to their adoption. In this paper, we propose a fast scalable QSTS simulation algorithm that is based on a linear sensitivity model for estimating voltage-related PV impact metrics of a three-phase unbalanced, nonradial distribution system with various discrete step control elements including tap changing transformers and capacitor banks. The algorithm relies on computing voltage sensitivities while taking into account all the effects of discrete controllable elements in the circuit. Consequently, the proposed sensitivity model can accurately estimate the state of controllers at each time step and the number of control actions throughout the year. For the test case of a real distribution feeder with 2969 buses (5469 nodes), 6 load/PV time series power profiles, and 9 voltage regulating elements including controller delays, the proposed algorithm demonstrates a dramatic time reduction, more than 180 times faster than traditional QSTS techniques.