Abstract

With the expansion of HVDC grids, short-circuit faults and their protection issues are among the main challenges of these networks, which should be given more attention. This study presents an investigation of the DC side fault current in HVDC grids during the transient period. Also, a fast and robust protection algorithm is introduced that is essential for secure and appropriate HVDC grids operation. The Short-Time Fourier Transform (STFT) is applied to extract the frequency components of the fault current, and the time features of these components are utilized as the basis of the proposed algorithm. A four-terminal cable-based HVDC grid with bipolar configuration is modeled via EMTP, and a wide range of simulation scenarios are applied for various fault locations, fault impedances, and operation points. Furthermore, the algorithm thresholds are determined with the explicit procedure. Simulation results indicate that the proposed method is fast, selective, sensitive, and robust against AC-side fault, operating condition variations, fault distance, and fault direction. Also, it has an appropriate performance during high impedance faults.

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.