Abstract

In the grid-connected inverter based on the deadbeat current control, the filter inductance variation and single update PWM affect the distortion of the grid current, stability, and dynamic of the system. For this, a double update PWM method for the deadbeat current controller in three-phase grid-connected system is proposed, which not only effectively decreases the grid current distortion and control delay, but also improves the system stability and dynamic response speed due to reducing the characteristic root equation order of the closed-loop transfer function. The influence of the filter inductance deviation coefficient on the system performance is analyzed. As a conclusion, the corresponding filter inductance deviation coefficient in the system critical stability increases with increase in the parasitic resistance of the filter inductance and line equivalent resistance and decreases with increase in the sampling frequency. Considering the system stability and dynamic response, the optimal range of the control parameters is acquired. Simulation and experimental results verify the effectiveness of the proposed method.

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.