Abstract

A direct maximum power point tracking (MPPT) method for PV systems has been proposed in this work. This method solves two of the main drawbacks of the perturb and observe MPPT, namely: 1) the tradeoff between the speed and the oscillations in steady-state and 2) the poor effectiveness in dynamic conditions, especially in low irradiance when the measurement of signals becomes more sensitive to noise. The proposed MPPT is designed for single-phase single-stage grid-connected PV inverters and is based on estimating the ripple of the instantaneous PV power and voltage, using a second-order generalized integrator-based quadrature signal generator. We analyzed the global stability of the closed-loop control system and validated the proposed algorithm through simulation and experiments on an inverter test platform according to the EN 50530 standard. The experimental results confirm the performance of the proposed method in terms of both speed and tracking efficiency.

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.