Abstract
In this paper, a novel determination method of defrosting start time based on frost accumulation amount tracking (FAAT) is proposed for air source heat pump systems. This method keeps tracking of the amount of newly deposited frost every time step using typical sensors adopted in the commercial heat pump systems. This is to predict the current volumetric blockage ratio in real-time and determine the defrosting start time. To develop the method, firstly, the reliability of the prediction results is validated with experimental data. Then, the feasibility of the suggested determination method is evaluated under various air ambient and system operating conditions. The result shows that the determination method has a root mean square error of 6.2% on a time basis and 5.1% on a capacity basis. Lastly, the influence of non-uniform frost distribution on the evaporator is investigated. It is shown that the determination method attains the robustness under varying frost non-uniformity.
Talk to us
Join us for a 30 min session where you can share your feedback and ask us any queries you have
Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.