Abstract

The flue gas of boiler contains large amount of waste latent heat, and traditional heat recovery device is difficult to recover the latent heat due to the limitation of the specific heat of supply air. A deep heat recovery device between flue gas and supply air of gas-fired boiler is proposed in the paper, and the thermodynamic model is established to calculate its performance. The energy efficiency of gas-fired boiler with the device is compared with other systems. The result shows that the boiler efficiency with new heat recovery device is 5% and 13% higher than that of condensing boiler and boiler without heat recovery system, respectively. When the ambient temperature is higher, the energy efficiency is closer to the boiler with absorption heat pump for heat recovery, and the initial investment is lower. Therefore, both the energy efficiency and economy of this system is acceptable.

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.