Abstract
One of the responses to the increasing penetration of renewable energies along with the growth in electricity demand is the interest in the construction of multi-terminal DC grids (MTDC), as mean to connect onshore AC systems with remotely located offshore wind energy sources. This paper investigates the current methodologies for MTDC control stating their limitations for severe contingency conditions and proposes a control strategy able to ensure grid reliability and voltage stability in the case of a sudden outage of the converter station controlled in Vdc-Q. This strategy, acting on the Vdc reference signal, allows the presence of multiple master converters in the DC grid. A five-terminal DC scheme, which connects onshore AC systems with offshore wind farms, has been developed in RT-Lab Simulator. Each sub-station (terminal) is equipped with a modular multilevel converter (MMC). The converters are either Vdc-Q controlled (master stations) or are P-Q (with droop control) or Vac-frequency regulated. The dynamic response of the system is observed after a converter outage to assess the validity of the proposed DC voltage control strategy.
Paper version not known (Free)
Published Version
Talk to us
Join us for a 30 min session where you can share your feedback and ask us any queries you have
Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.