Abstract

With increased use of programmable logic controllers (PLCs) in implementing critical systems, quality assurance became an important issue. Regulation requires structural testing be performed for safety-critical systems by identifying coverage criteria to be satisfied and accomplishment measured. Classical coverage criteria, based on control flow graphs, are inadequate when applied to a data flow language function block diagram (FBD) which is a PLC programming language widely used in industry. We propose three structural coverage criteria for FBD programs, analyze relationship among them, and demonstrate their effectiveness using a real-world reactor protection system. Using test cases that had been manually prepared by FBD testing professionals, our technique found many aspects of the FBD logic that were not tested sufficiently. Domain experts, having found the approach highly intuitive, found the technique effective.

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.