Abstract

AbstractA data‐driven approach is developed and proven for ranking the risk of low disinfection residual in water distribution storage tanks, 1 month ahead. The forecasting methodology uses water quality data collected from drinking water treatment plants, storage tank outlets, and rainfall data as inputs. This methodology was developed and tested with data from a water utility serving more than 5 million people. Results show high‐risk category prediction accuracy of 75%–80%. Using a final year of unseen validation data, more than 90% of the storage tanks ranked in the top 20 by the forecasting methodology experienced low disinfectant residual in the following month. Storage tanks are critical water distribution system infrastructure that are currently managed reactively. The adoption of such readily transferable machine learning approaches enables direct proactive management strategies and efficient interventions that can help ensure drinking water quality.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.