Abstract

A current transformer saturation identification method of transmission line based on current sample data is proposed in this paper. Mechanism and characteristics of current transformer saturation are analyzed firstly. Current transformer saturation identification plane is proposed. It is divided into three parts: internal fault zone, external fault zone and current transformer saturation zone caused by external faults. For current transformer saturation caused by external faults, current differential protection is blocked. The RTDS simulation results show that the method can identify CT Saturation quickly and sensitively. It is not impacted by data window length.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.