Abstract
A medium power Current Source Converter (CSC) based Active Power Filter (APF) system is designed and implemented to suppress the amplification of low order harmonics at the Medium Voltage (MV) interface bus between the distribution and transmission systems, owing to the presence of large shunt capacitor banks installed only for reactive power compensation. For this purpose, four CSC based APF units designed at 1.0 kV are operated in parallel, and connected to the 31.5 kV MV bus via a specially designed coupling transformer. In each APF module, a specially designed LC-type input filter eliminates the switching ripples, and active damping method embedded into the control software suppresses harmonic frequencies around the natural frequency of the input filter. The resulting system can operate at relatively high frequencies in the range from 2.0 to 3.0 kHz, depending upon which selected harmonics among 5th, 7th, 11th, and 13th are to be eliminated. Furthermore, in order to reduce the installed capacity of CSCs, Selective Harmonic Amplification Method (SHAM) is applied to the APF system described in the paper. MV APF system has been built as a mobile system for temporary connection to a problematic MV interface bus, until a permanent solution is found for that location in the distribution system.
Talk to us
Join us for a 30 min session where you can share your feedback and ask us any queries you have
Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.