Abstract
A method of symmetrical component analysis for the detection of current-transformer (CT) saturation in a numerical current differential feeder protection relay is presented in this paper. The performance of the differential relay is investigated for various faults on a typical Electro-Magnetic Transients Program/Alternative Transients Program (EMTP/ATP) simulated transmission feeder. The simulator includes the effects of CT saturation. A comparison between simulation and tests conducted on an analog model testbench are also evaluated. The results show a high degree of similarity and illustrate the effect that CT saturation imposes on the sensitivity and stability of the protection scheme. An algorithm is presented that shows significant improvement in sensitivity on internal faults while still maintaining a high level of stability on external faults and nonfault events.
Talk to us
Join us for a 30 min session where you can share your feedback and ask us any queries you have
Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.