Abstract

This paper proposes a new approach for reducing inrush currents in three-phase-three-legged stacked core power transformers. Although magnitudes of inrush currents may not be as high as short circuit currents, they are extremely detrimental to normal operation of power transformers. In this paper, a new controlled switching scheme that takes into consideration both core saturation and residual flux is proposed to reduce inrush currents. Also, a transient model based on the duality transformation between electric and magnetic circuits is proposed where a non-linear inductance is used to simulate core saturation. The proposed scheme is demonstrated on a real transformer by both laboratory experiments and performing simulations. In the simulation phase, the alternative transients program (ATP) is used to simulate a wide spectrum of possible operating conditions. The experimental and simulation results show that inrush currents are significantly reduced after utilizing the proposed scheme. Therefore, the proposed controlled switching scheme will result in relaxing inrush current related constraints in designing and manufacturing three-phase power transformers which in turn will reduce their cost.

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.